| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| A security issue exists due to improper handling of malformed CIP packets during fuzzing. The controller enters a hard fault with solid red Fault LED and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF019. To recover, clear the fault. |
| A code execution security issue exists in the affected product. An attacker with physical access could abuse the maintenance menu of the controller with a crafted payload. The security issue can result in arbitrary code execution. |
| A security issue was discovered within Verve Asset Manager allowing unauthorized read-only users to read, update, and delete users via the API. |
| A security issue exists within 432ES-IG3 Series A, which affects GuardLink® EtherNet/IP Interface, resulting in denial-of-service. A manual power cycle is required to recover the device. |
| A security issue was discovered within the legacy Ansible playbook component of Verve Asset Manager, caused by plaintext secrets incorrectly stored when a playbook is running. This component has been retired and has been optional since the 1.36 release in 2024. |
| An
authentication bypass vulnerability exists in the affected product. The
vulnerability exists due to shared secrets across accounts and could allow a threat
actor to impersonate a user if the threat actor is able to enumerate additional
information required during authentication. |
| A security issue exists within DataMosaix™ Private Cloud, allowing attackers to bypass MFA during setup and obtain a valid login-token cookie without knowing the users password. This vulnerability occurs when MFA is enabled but not completed within a 7-day period. |
| A local code execution security issue exists within Studio 5000® Simulation Interface™ via the API. This vulnerability allows any Windows user on the system to extract files using path traversal sequences, resulting in execution of scripts with Administrator privileges on system reboot. |
| A denial-of-service security issue in the affected product. The security issue occurs when a malformed CIP forward open message is sent. This could result in a major nonrecoverable fault a restart is required to recover. |
| Studio 5000 Logix Designer 30.01.00 contains an unquoted service path vulnerability in the FactoryTalk Activation Service that allows local users to potentially execute code with elevated privileges. Attackers can exploit the unquoted path in C:\Program Files (x86)\Rockwell Software\FactoryTalk Activation\ to inject malicious code that would execute with LocalSystem permissions. |
| CVE-2024-6078 IMPACT
An improper authentication vulnerability exists in the affected product, which could allow a malicious user to generate cookies for any user ID without the use of a username or password. If exploited, a malicious user could take over the account of a legitimate user. The malicious user would be able to view and modify data stored in the cloud. |
| A vulnerability exists in the Rockwell Automation Emulate3D™, which could be leveraged to execute a DLL Hijacking attack. The application loads shared libraries, which are readable and writable by any user. If exploited, a malicious user could leverage a malicious dll and perform a remote code execution attack. |
| An improper authorization vulnerability exists in the Rockwell Automation affected products that could allow an unauthorized user to sign in. While removal of all role mappings is unlikely, it could occur in the case of unexpected or accidental removal by the administrator. If exploited, an unauthorized user could access data they previously but should no longer have access to. |
| A security issue exists in FactoryTalk ViewPoint version 14.0 or below due to improper handling of MSI repair operations. During a repair, attackers can hijack the cscript.exe console window, which runs with SYSTEM privileges. This can be exploited to spawn an elevated command prompt, enabling full privilege escalation. |
| A Local Privilege Escalation vulnerability exists in the affected product. The vulnerability requires a local, low privileged threat actor to replace certain files during update and exists due to a failure to perform proper security checks before installation. |
| A security issue exists due to improper handling of malformed CIP Forward Close packets during fuzzing. The controller enters a solid red Fault LED state and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF015. To recover, clear the fault. |
| A Remote
Code Execution vulnerability exists in the affected product. The vulnerability requires
a high level of permissions and exists due to improper input validation resulting
in the possibility of a malicious Updated Agent being deployed. |
| A denial-of-service security issue exists in the affected product and version. The security issue is caused through CIP communication using crafted payloads. The security issue could result in no CIP communication with 1715 EtherNet/IP Adapter.A restart is required to recover. |
| A denial-of-service vulnerability exists via the CIP/Modbus port in the Rockwell Automation Micro850/870 (2080 -L50E/2080 -L70E). If exploited, the CIP/Modbus communication may be disrupted for short duration. |
| A local server-side request forgery (SSRF) security issue exists within Studio 5000® Simulation Interface™ via the API. This vulnerability allows any Windows user on the system to trigger outbound SMB requests, enabling the capture of NTLM hashes. |