P-Net before 1.0.4 sets the alarm receiver state to waiting for confirmation before the data of a received alarm notification is parsed. If the parsing fails the state is not restored, and later alarm notifications of the same priority are discarded without acknowledge until the Application Relationship is released. The Application Relationship and the cyclic data exchange keep working. The attacker must be able to send an alarm notification in the context of an established Application Relationship and requires ADJACENT network access.
Project Subscriptions
No data.
Advisories
No advisories yet.
Fixes
Solution
Upgrade to P-Net 1.0.4 or later.
Workaround
No workaround given by the vendor.
References
History
Fri, 13 Nov 2026 13:30:00 +0000
| Type | Values Removed | Values Added |
|---|---|---|
| Description | P-Net before 1.0.4 sets the alarm receiver state to waiting for confirmation before the data of a received alarm notification is parsed. If the parsing fails the state is not restored, and later alarm notifications of the same priority are discarded without acknowledge until the Application Relationship is released. The Application Relationship and the cyclic data exchange keep working. The attacker must be able to send an alarm notification in the context of an established Application Relationship and requires ADJACENT network access. | |
| Title | Alarm receiver stops delivering alarms after a malformed alarm notification | |
| Weaknesses | CWE-754 | |
| References |
| |
| Metrics |
cvssV4_0
|
Projects
Sign in to view the affected projects.
Status: PUBLISHED
Assigner: rt-labs
Published:
Updated: 2026-11-13T13:23:45.251Z
Reserved: 2026-11-09T12:48:59.072Z
Link: CVE-2026-124760
No data.
Status : Deferred
Published: 2026-11-13T14:17:50.480
Modified: 2026-11-13T14:17:50.573
Link: CVE-2026-124760
No data.
OpenCVE Enrichment
No data.
Weaknesses